The weather has gradually turned cold, and it is very important to maintain a diesel generator set after entering the winter. After all, the price of a generator set is very high, from tens of thousands to hundreds of thousands. If improperly maintained, it will lead to unpredictable consequences. Therefore, the Guangxi Zhengchai Generator Group once again announced the measures for “how to maintain the diesel generator set in winter”. Let you worry about spending the winter!
Pictured below: Picture of YC6TD840L-D20 unit
Level 1 technical maintenance: (50-80 hours) increase in the content of daily maintenance
1. Clean the air filter and replace if necessary;
2. Replace the diesel filter, air filter, water filter;
3. Check and check the tension of the transmission belt;
4. Add lubricant to all grease fittings and lubrication parts;
5, replace the cooling water
Secondary technical maintenance: (250-300 hours) added to the daily maintenance and first-level maintenance content
1. Clean the piston, piston pin, cylinder liner, piston ring and connecting rod bearing and check the wear and tear;
2. Check whether the inner and outer rings of the rolling main bearing are loose;
3. Remove scale and sediment from the water channel of the cooling water system;
4. Remove the carbon deposits in the cylinder combustion chamber and the intake and exhaust ducts;
5. Check the wear and tear of the valve, valve seat, push rod and rocker arm, and adjust the grinding;
6. Clean the supercharger of the turbocharger rotor, check the bearing and impeller wear, and replace it if necessary;
7. Check if the bolts of the generator and diesel engine coupling are loose or slippery, and the problems should be repaired.
Three-level technical maintenance: (500-1000 hours) increased in daily maintenance, primary maintenance, secondary maintenance content
1. Check and adjust the fuel injection angle;
2, cleaning the fuel tank;
3. Clean the oil pan;
4. Check the atomization of the injection nozzle